黄h视频在线观看视频,要爽死国产一区在线播放,www.欧美在线,奇米影视一区二区三区 ,成人国产精品一区二区八戒网,精品亚洲AV毛片高清,精品先锋中文字幕,欧美日韩精品激情在线看 ,内射极品美女少妇久久精品免费一级一片一毛片-女明星的

Contact Us

Blower Fan guide vane adjustment method

Date: 2016-5-20   Click: 1840 Times

"Blower Fan" inlet guide vane adjustment device that is in the vicinity of the blower suction inlet provided a set of adjustable vanes corner - the inlet guide vane, its role is to take place in the gas stream before entering the rotating impeller, causing distortion speed. Vanes can be rotated about its own axis, a rotation angle of each blade means converting a vane mounting angle, so that the direction of air flow into the fan impeller changed accordingly. "Blower Fan" centrifugal fan with inlet guide vane adjustment method, a high efficiency and a wide range of performance at part load operation, while maintaining a constant outlet pressure conditions, the work flow can be 50% to 100% of the rated flow rate in the range of Variety. Adjust the depth of the greater, the more the provincial power. "Blower Fan" such as reducing the flow to 60% of the rated flow rate when the inlet guide vanes way than the meter-way power savings of up to 17 percent.